High Temperature Self Regulating Heat Tracing Cable
Marathon Heaters self regulating heating cable provide the most versatility in heat trace design and applications. Constructed of a Semi-conductive heater matrix extruded between parallel buswires, a self regulating cable adjusts its output to independently respond to ambient temperatures all along its length. As temperatures increase,the heater’s resistance increase which lower the output wattage. Conversely, as the temperature decrease, the resistance decreases and the cable produces more heat. So it is no need thermostat in some applications. It will never overheat or burnout even when wrapped by itself(overlapped). It can be cut to any length. So it is a convenient ,easy use and energy saving product.
Construction
1. Bus wires
2. Semi-conductive self regulating matrix
3. Inner Jacket
4. Copper /Nickle plated copper
5. Outer Jacket
Construction Data
Buswire size | 1.5mm nickel copper |
Heating elements | Fluoropolymer heating mixture |
Insulation | Fluoropolymer/FEP |
Braiding | Tinned copper |
Outjacket | Fluoropolymer/FEP |
Graph of HTSRH
Max length(m)vs circuit breaker size
AC220V | Max circuit length(m) vs CB size | |||
Model | Start-up temp.°C | 32A | 40A | |
HTSRH | 10 | 53 | 66 | |
0 | 48 | 60 | ||
-20 | 44 | 55 | ||
-40 | 39 | 49 |
Output wattage at 10°C | 40, 55, 60, 65 W/M |
Braiding covering area | Over 85% |
Max. maintain temp @ 10°C | 135°C |
Max. exposure temp. | 205°C |
Min.installation temp. | -40°C |
Bending radius | 10 times*cable thickness |
Voltage | 110-120/208-277 V |
Insulation color | Dark Grey |
Regular size to insulation | 9.8*3.3 mm (Width*Thickness) |